Ventilation rates of air conditioners in different rooms for various living scenarios

Time:2021-10-17 20:08   Author:Publicity Center

1. Ventilation rate of air conditioner

Although more air exchange is better, it will lead to an increase in equipment size, which will create a huge financial burden, especially when dealing with external atmospheres and heating or cooling. Therefore, the amount of air exchange should be limited to the minimum required amount. There was a significant relationship between air exchange rate and smoking in the absence of job contamination and only worker contamination. If the amount of smoked is less than the amount of smoked per hour or "occasional smoking" level, the air exchange rate is 10-15m? /(h··(H·), slightly more is 20-25m³/(h·(H·). For entertainment and party places where each person smokes more than 2 cigarettes per hour, the minimum required air rate is 40-50m³/(H··(H·person)), and the appropriate air rate is about 1.5 times. Usually, the standard is 35m³/(H·person).

2. Advice on various situations

When the indoor occupants are unsure, obtain the air exchange rate per square meter of floor area [m sand/(h·(h·(h·(H·)))) from the table below:

room type Ventilation rate (M³/h·㎡)
residential room 8
office 10
Duty room 12
exhibition room 12
dressing room 12
small shop 15
studio 15
entertainment lounge 15
smoking room 20
small meeting room 25
Commercial canteen 25
Business kitchen 60
kitchen table 25
Non-corporate canteen 20
Non-commercial kitchen 35
hot water room 15
locker room 10
public bathroom 20
family bathroom 20
public restroom 30
family toilet 20
bathroom 10
screening room 20
Dust smell room 30
gas chamber 35 photography darkroom 20 Mechanical and electrical room 10